The bulk erase process for 1.x EP/LP firmware is:
- Configure Dip Switch 1 and 2 ON and 3 and 4 OFF
- Power up panel
- Within a few seconds LEDs 1 & 2 and 3 & 4 to alternately flash ON/OFF
- Within 10 seconds after the above pattern starts, change switch 1 to OFF
- All LED's will be off for several seconds seconds and then LEDs 1 & 4 will flash for about 3 seconds indicating the erase process has completed.
The bulk erase process for 2.x firmware is the same as 1.x with the difference there are longer wait times in-between steps:
- Configure Dip Switch 1 and 2 ON and 3 and 4 OFF
- Reset/Apply power to the panel. LED 1 will flash on for 55 seconds while the panel boots up.
- After the 55 second boot, LEDs 1 & 2 and 3 & 4 to alternately flash ON/OFF
- Within 10 seconds after the above pattern starts, change switch 1 to OFF
- All LED's will be off for several seconds seconds and then LEDs 1 & 4 will flash for about 3 seconds indicating the erase process has completed.